If the pilot burner flame extinguishes during the run state

(flameout), the control de-energizes the pilot and main gas

valve for the interpurge period. After this period, another

trial for ignition is initiated. If the flameout cycle repeats for a

total of 16 times (pilot burner flame established then lost), the

control will:

• Enter the lockout mode if the control is a G770/G777. The

thermostat contacts must be opened for 30 seconds and

then closed to escape the lockout condition.

• Enter the shutoff mode and recycle period (5 minute

recycle delay for the G775/G779 and 60 minute recycle

for the G776/G778) before beginning another trial for

ignition, starting with prepurge.

Wiring Diagram For Integral Spark/Sense Without Vent Damper

GROUND

5

24 V

LED

THS 2

PV 1

MV 3

Transformer

Pilot Burner

Assembly

Integral

Igniter/Sensor

Main Burner

Ground

Pilot

Gas Supply

Pilot

Valve

Main

Valve

Ignition Control

Limits in Thermostat

Line Only