SBD TANK TYPE HEATERS

SERVICE HANDBOOK

Technical Training Department

Ashland City, TN ©2003

16

SBD SEQUENCE OF OPERATION

1. Thermostat calls for heat

2. Flue damper opens

3. Intermittent

Ignition Control

5. Main gas valve opens

7. Thermostat satisfies

4. Pilot gas opens,

Pilot sparks and

flame proves

6. Main burner ignites

8. Main and pilot

burners "OFF"

SEQUENCE OF OPERATION

To understand SBD tank type water heaters, an examination of their sequence of

operation is necessary.

When the thermostat calls for heat, the relay in the draft hood assembly activates the

flue damper motor. The damper opens and power flows to the IID (Intermittent

Ignition Device). This activates the IID module to open the pilot valve and begin

sparking at the pilot burner assembly. Once the pilot flame is established and

confirmed back to the IID, the sparking is stopped and the main gas valve is opened,

allowing gas flow to the main burner. When the thermostat satisfies, main and pilot

gas is shut off. Damper is returned to closed position.

9. Flue damper closes