SBD TANK TYPE HEATERS

SERVICE HANDBOOK

Technical Training Department

Ashland City, TN ©2003

4

EXTERIOR CLEARANCE

This illustrates the exterior roof clearances for SBD units with natural draft venting. The

vent shall extend at least 3 feet above the highest point where it passes through a roof of

a building, and at least 2 feet higher than any portion of a building within a horizontal

distance of 10 feet (for vents of 12" in diameter or less). (NFPA 54 ANSI Z 223.1 SEC

7.5.2a). (Sec 7.6.2a may allow reduction to 8 feet with a “ Listed vent cap”).

"Copyright by the American Gas Association. Used by permission of the copyright holder".