SBD TANK TYPE HEATERS

SERVICE HANDBOOK

Technical Training Department

Ashland City, TN ©2003

23

STEP 6

PC BOARD MOTOR TEST

STEP 6. PC BOARD/MOTOR TEST. Check for 24 VAC between the two motor lead

terminals of the PC board. Disconnect the wires for this test.

N

E

H

T

F

I

24 VAC is not present:

• Replace the Damper Drive and go to

step 7. The board and relay are

one piece. Regardless of which

part is defective, both parts

should be changed.

Voltage is present:

This verifies that the motor is receiving

power but not closing the damper.

Replace the Damper Drive and go to

step 7.

Note: The service switch may be used to bypass the damper, while waiting for a replacement part.

WARNING - In the event of damper motor failure, verify that the damper is in the "open"

position before utilizing the service switch

Service Switch

Motor Lead

Motor Lead