SBD TANK TYPE HEATERS

SERVICE HANDBOOK

Technical Training Department

Ashland City, TN ©2003

7

MAKE-UP AIR

VERTICAL DUCTS

Often it is more practical to install vertical make-up air ducts to the out doors. Again, two

openings are required - one within 12 inches of the top of the enclosure and one within

twelve inches of the bottom of the enclosure. Each opening shall have a free area of not

less than 1 square inch per 4000 BTUH of the total input of all appliances within the

enclosure.

MAKE-UP AIR

HORIZONTAL DUCTS

When the heater is installed in an interior room with no roof access for vertical ducts,

horizontal make-up air ducts should be installed. When using horizontal ducts, two

openings are required - one within 12 inches of the top of the enclosure and one within

twelve inches of the bottom of the enclosure. Each opening shall have a free area of not

less than 1 square inch per 2000 BTUH of the total input of all appliances within the

enclosure.

1 Square

Inch Per

4,000

BTUH

1 Square

Inch Per

2,000 BTUH