SBD TANK TYPE HEATERS

SERVICE HANDBOOK

Technical Training Department

Ashland City, TN ©2003

20

STEP 2

HIGH LIMIT, LEFT TERMINAL TEST

STEP 2. HIGH LIMIT, LEFT TERMINAL TEST. Test for 24 VAC between the left high

limit terminal and ground.

N

E

H

T

F

I

The meter does not read 24 VAC:

• Check wiring between transformer and

high limit.

The meter reads 24 VAC:

• Go to Step 3.

Note: The high limit (Energy Cut Off) opens if the tank water temperature exceeds 205

degrees. The control is resettable (manually) when the tank water temperature drops

below 185 degrees.

Ground

24 VAC

FM Transformer