SBD TANK TYPE HEATERS

SERVICE HANDBOOK

Technical Training Department

Ashland City, TN ©2003

5

AIR FOR COMBUSTION

10 CUBIC FEET OF AIR PER 1,000 BTU

Stoichiometric or theoretical complete combustion requires 10 cubic feet of air per 1000

BTUH input of the gas input. The National Fuel Gas Code also recommends an

additional 2.5 cu.ft. of "excess" air. This 12.5 cu.ft minimum supply air per 1000 BTUH

input applies to natural and propane gas models.

The National Fuel Gas Code also specifies minimum make-up air opening sizes for

various building installations. (Ref: NFPA 54, ANSI Z223.1, sec 5.3)

2.5 CU.

FT.

EXCESS

AIR

+

10 CU.

FT.

COMB.

AIR

(Minimum)

1,000

BTU