Any changes made to the panels that have not been agreed with the maker shall
automatically invalidate the warranty.


CHECKING THE GOODS

Upon receipt of the unit, make sure that what is received corresponds with what is specified

in the shipping documents accompanying the unit.

SAVE ALL THE DOCUMENTATION PROVIDED.

STORE DOCUMENTS CAREFULLY IN A DRY LOCATION!

1 - Electronic control unit

Display of alarms and status, battery voltage,

speedometer, hour counter, alarm

programming, date display, main signals and
manual start button.

2 - Key-operated 3-position selector switch

“Manual - Automatic- 0”

- Manual mode: enabling of

START/STOP/ENTER pushbuttons on the

control unit, with possibility of starting and

stopping the engine.

During pump operation, the alarms shown can

stop the engine; when the engine is stopped,

the set-up configuration can be accessed.

- Automatic mode: the only buttons enabled

on the power unit are STOP and RESET. The
motor is automatically started when the input

contact (starting pressure switch) is opened,

while it is stopped manually by pressing the

STOP button (the STOP button only works if

the starting pressure switch status has

returned to the closed position). Stopping is

manual apart from the diesel engine version

for systems with hydrants for which stopping

is automatic.

The alarms displayed do not stop the motor but are only signalled; to reset them press the

RESET button provided that the alarms that generated them have been eliminated and the
motor has stopped.

- Shutdown mode “0”: the motor pump cannot be started manually or automatically from

the electronic control unit. If the engine is running, immediate shut-off occurs.

3 (4) - Battery emergency start button 1(2) This button starts the engine directly from battery

1 (2); use only in case of an emergency.

5 - Main switch

Switch for power supply from the line

WARNING