- ADDITIONAL INPUT PROGRAMMING

In addition to the standard inputs with dedicated terminal, such as fuel reserve, low engine

oil pressure, high engine temperature, etc… (see electrical panel wiring diagram) it is possible

to select up to three additional inputs, identified below as “IN AUX1, IN AUX2, IN AUX3”.

FUNCTION

SELECTABLE

FIELDS

DEFAULT

SETTINGS

NOTES*

Operating Mode

“Oper. Mode IN AUX 1”

000 / 015

015

000 = Disabled

001 = AUX 1 input alarm

004 = Heater / Battery charger alarm

005 = Remote start command

015 = Pump pressure alarm (NO)

Operating Mode

“Oper. Mode IN AUX 2”

000 / 015

000

000 = Disabled

002 = AUX 2 input alarm

004 = Heater / Battery charger alarm

005 = Remote start command

015 = Pump pressure alarm (NC)

Operating Mode
“Oper. Mode IN AUX 3”

000 / 015

000

000 = Disabled

003 = AUX 3 input alarm
004 = Heater / Battery charger alarm

005 = Remote start command

015 = Pump pressure alarm (NC)

*Notes:

- AUX 1, AUX 2: Digital inputs available on electric panel’s X1 terminals, for connection of

device with ground reference

- AUX 3: Digital input available on the terminals of the control unit’s electronic card, for

connection of device with ground reference.

- Remote start command: with this setting the motor pump starts when the status of the

input signal changes, and it stops as soon as the status returns to its original condition.

IMPORTANT: the default setting for all the “IN AUX2, IN AUX3” programmable inputs is

“000” disabled.