PROGRAMMING OF RELAY OUTPUTS


In addition to the “dedicated relay” status outputs, such as automatic disabled, failure to
start, pump running, controller fault, fuel reserve, etc…, and “alarm summary relay” (see
electrical panel wiring diagram), two status relay outputs “OUT AUX 1, OUT AUX 2” are
available for programmed inputs “IN AUX1, IN AUX2, IN AUX3”.

FUNCTION

SELECTABLE

FIELDS

DEFAULT

SETTINGS

NOTES

Operating Mode

“Oper. Mode

OUT AUX1”

000/016

015

000 = Disabled

001 = IN AUX 1 input alarm
002 = IN AUX 2 input alarm

003 = IN AUX 3 input alarm

004 = Heater / Battery charger alarm

005 = Remote start command

006 = Low engine oil pressure alarm

007 = High engine temperature alarm

008 = Panel supply voltage failure alarm

009 = Low battery voltage alarm

010 = Engine rpm alarm

015 = Pump pressure alarm

016 = Pump running

Operating Mode

“Oper. Mode

OUT AUX2”

000/016

000

000 = Disabled

001 = IN AUX 1 input alarm

002 = IN AUX 2 input alarm

003 = IN AUX 3 input alarm

004 = Heater / Battery charger alarm

005 = Remote start command

006 = Low engine oil pressure alarm

007 = High engine temperature alarm

008 = Panel supply voltage failure alarm

009 = Low battery voltage alarm

010 = Engine rpm alarm

015 = Pump pressure alarm
016 = Pump running

IMPORTANT:
- The relay activates, closes the contact, when an alarm condition occurs.