Xylem Motor pump control unit GEN Series User Manual
Page 42
![background image](/manuals/310547/42/background.png)
42
FUNCTION
SELECTABLE
FIELDS
DEFAULT
SETTINGS
NOTES
“Panel Vdc voltage”
Start batteries DC
voltage setting
000/001
000
000 = 12 Vdc
001 = 24 Vdc
“Crown gear teeth”
speedometer
calibration setting
000/999
-
The value shown corresponds to
the number of teeth on the
engine’s crown gear, where the
sensor is located
“Low engine rpm
threshold”
0000/9999
2500
Engine rpm alarm threshold
“Operating hours”
0000/9999
-
Number of motor pump
operating hours, which can be
modified if boards are replaced
“Enable weekly”
Activation of self-
testing mode
000/001
000
000 = Disabled
001 = Enabled
“Enable UNI10779”
Activation of auto
shut-off mode
000/001
000
000 = Disabled
001 = Enabled
“Address 232”
Communication port
000/999
001
Specify address only for systems
with multiple control units
connected