Xylem Motor pump control unit GEN Series User Manual

Page 36

Advertising
background image

36

No
alternating

voltage Vac

Display

Programmable relay

+ Alarm summary relay

Continuously Permanent

Low battery

voltage

Display

Programmable relay

+ Alarm summary relay

Continuously

Low battery level

12Vdc =alarm at 10Vdc

24Vdc =alarm at 22Vdc

Non-

automatic

selector

switch

Display +

Red Indicator

Led

Dedicated relay

+ Alarm summary relay

Continuously

Failure to
start

Display +

Red Indicator
Led

Dedicated relay
+ Alarm summary relay

Continuously

Alarm triggers after

failure of 6
automatic attempts

to start. Permanent

Pump

running

Display +

Red Indicator

Led

Dedicated relay

+ Alarm summary relay

Continuously

Controller

fault

Display +

Red Indicator

Led

Dedicated relay

+ Alarm summary relay

Continuously

Fuel reserve

Display

Dedicated relay

+ Alarm summary relay

Continuously

Triggering

of Heater or
Battery

charger

protections

Display

Programmable relay

+ Alarm summary relay

Continuously Permanent

IN-AUX1,

IN-AUX2,

IN-AUX3

signal

Display

Programmable relay

+ Alarm summary relay

Continuously

* Notes:

- Engine running: the control unit recognizes the engine running status only if the

speedometer indicates a speed exceeding 600rpm. Do not modify the “Crown gear
teeth” setting.

- Engine status alarm: “Low engine oil pressure and High engine temperature” 10 seconds

after the engine is started.

- No VAC voltage alarm 1 second after the value has been measured.

- Low battery voltage alarm 60 seconds after the value has been measured.
- Alarms can be reset using the RESET button for 5 sec, provided that the problem that

triggered the alarm has been eliminated.