6. TROUBLESHOOTING

After performing the user troubleshooting checks:

The control unit does not switch

on

Batteries partially charged: check and recharge the

batteries; replace them if necessary.

QU3 fuse carrier open or blown fuse: check the fuse carrier

and, if necessary, replace the fuse

Connections to battery terminals corroded or loose: clean,

examine and tighten the nuts on the battery terminals.

Replace the cable terminals and nuts if they are too

corroded

Alternating voltage failure alarm Line power failure: check the line wire and voltage.

QU1 fuse carrier open or blown fuses: check the fuse

carrier and, if necessary, replace the fuses

A battery voltmeter shows no

voltage

Battery disconnected: Connections to battery terminals

corroded or loose: clean, examine and tighten the nuts on

the battery terminals. Replace the cable terminals and nuts

if they are too corroded.

Install a new battery if not present.

Internal battery charger alarm

(alarm LED on)

Reversed polarity: disconnect the battery and reconnect

properly

Battery disconnected: Connections to battery terminals

corroded or loose: clean, examine and tighten the nuts on

the battery terminals. Replace the cable terminals and nuts

if they are too corroded.

Install a new battery if not present.

Shorted terminals: replace the battery or, if it is still

efficient, restore the connections.

Battery voltage value too low: replace the battery

Internal battery charger off

(LEDs off)

Line power failure: check the line wire and voltage

QU1 fuse carrier open or blown fuses: check the fuse

carrier and, if necessary, replace the fuses

Starting relay blown

With the selector switch in MAN

position and the START button

depressed, the motor pump

does not start

Batteries discharged or disconnected: Connections to

battery terminals corroded or loose: clean, examine and

tighten the nuts on the battery terminals. Replace the

cable terminals and nuts if they are too corroded.

Install a new battery if none is present or if the one being

used is discharged

Both starting relays blown
Control unit failure

With the selector switch in AUTO

position and the start contact

active the motor pump does not

start

Batteries discharged or disconnected: Connections to

battery terminals corroded or loose: clean, examine and

tighten the nuts on the battery terminals. Replace the

cable terminals and nuts if they are too corroded.

Install a new battery if none is present or if the one being

used is discharged

Both starting relays blown