Xylem Motor pump control unit GEN Series User Manual

Page 35

Advertising
background image

35

“0”: FUNCTION SHUTDOWN

Key-operated selector switch in “0” position

Normally it is left in the AUTO position with the key out.

If the key-operated selector switch is set to “0”, the engine shuts off if it is running

IMPORTANT: the motor pump cannot be started manually or

automatically from the electronic control unit. Use this mode when

performing maintenance operations.

The two green emergency start buttons on the control panel are in any case

enabled to start the engine. Follow the safety regulations to avoid any accidental
start-ups of the engine; if necessary disconnect the batteries.

Electronic control unit indicator lights

Red AUTOFUNCTION OFF indicator light on.

Red FAILURE TO START indicator light off.

Red PUMP RUNNING indicator light off

Red CONTROLLER FAULT indicator light off

The following information is displayed:

- “0” mode
- Selector switch not set to automatic mode
- Battery voltage

Note: if the key-operated selector switch is in the “0” position, it is not possible to program

the control unit.

4. ALARMS AND SIGNALS

A number of control and alarm signals are available on the control unit.

DESCRIPTION

DISPLAY

OUTPUT SIGNAL

ENABLED

NOTES*

Low engine

oil pressure

Display

Programmable relay

+ Alarm summary relay

With engine

running

Permanent

High engine

temperature Display

Programmable relay

+ Alarm summary relay

With engine

running

Permanent

Low engine

rpm

Display

Programmable relay

+ Alarm summary relay

With engine

running

Permanent

Overspeed

“RUNAWAY” Display

Programmable relay

+ Alarm summary relay

With engine

running

Permanent

WARNING