X1 – STATUS RELAY TERMINALS

CODE

DESCRIPTION

OUT AUX1

Output activated by alarm programmed from set-up

OUT AUX2

Output activated by alarm programmed from set-up

OUT RIS.

Output activated if “IN RIS.“ input is connected to ground

ALARM

Alarm summary output. Output activated by at least one of the following

alarms:

- Automatic operation disabled

- Engine running

- MP06 control board fault

- Engine failure to start

- Low fuel level

- Low engine oil pressure

- High engine temperature

- No AC voltage

- Low Battery 1 or 2 voltage

- Low engine rpm

- Engine overspeed (runaway)

- Triggering of Heater and/or Battery charger protection

- Input signal IN AUX1

- Input signal IN AUX2

- Input signal IN AUX3

- Fuel reserve

NO AUTO

Output activated by Selector switch not in Automatic mode position

NO START

Output activated in case of failure of 6 automatic attempts to start engine

MOTOR ON Output activated by engine running status

FAULT NC

Output activated by control unit alarm for:
- software alarm

- hardware alarm

- No Vdc power supply voltage alarm

NO contact available on control unit terminal board

FAULT NO

COM

Relay outputs common