5. ELECTRICAL PANEL CONTROL TERMINALS

X1 - ANALOGUE AND DIGITAL INPUT TERMINALS

CODE

DESCRIPTION

B1+

Analogue signal input for battery 1 voltage value

B2+

Analogue signal input for battery 2 voltage value

B-

Common input for battery negatives and others

AV1

Starting relay 1 command output

AV2

Starting relay 2 command output

STOP

Engine shut-off device command output

BPO

“Low Engine Oil Pressure” signal input. The input is enabled by the controller

10 seconds after the engine has been started

ATA

“High Engine Temperature” signal input. The input is enabled by the

controller 10 seconds after the engine has been started

IN RIS.

“Low Fuel Level” signal input

CB

Battery charger voltage input from engine

PK

Frequency signal input (PICK-UP) for engine speed measurement

PK-

PICK-UP reference (ground)

PRESS-

Pressure switch start contact signal reference (ground)

PRESS

Pressure switch start contact signal input

IN AUX1

Digital signal input active, programmable from set-up

IN AUX2

Digital signal input active, programmable from set-up

IN AUX3

Digital signal input active, programmable from set-up. Available directly on

electronic control unit terminal board

QF1

Alternating power supply voltage input for panel internal devices. Phase,
neutral and ground (yellow/green) cables must be connected to

corresponding PE terminal

QU2

Alternating power supply output for engine heating device HEATER

RS232

RS232 connector for connection to PC (or similar) for event memory transfer

or download via a dedicated software

Note: For terminal numbering see diagram attached to electrical panel