EVENT MEMORY DOWNLOAD

This function makes it possible to transfer the alarms stored during the operation of the

motor pump.

An RS232 communication port is available as standard for connection of external interface.

Possibility of connection to a PC or similar device via dedicated software, available upon

request. Cable not included.

FUNCTION

SELECTABLE

FIELDS

DEFAULT

SETTINGS

NOTES

“Events download”

000/001

000

000 = Disabled
001 = Enabled with display of

message: “DOWNLOAD

IN PROGRESS”

FIRST COMMISSIONING

This function, with the selector switch in the “MAN” position, is used to activate a procedure

that provides for six automatic start-up attempts, each lasting no less than 15 sec, with the

starter running and a time pause of 10 to 15 seconds.

At the end of the attempts an alarm is triggered, a failure to start signal is activated and a
yellow indicator light comes on under the START button. Press the START button to start the

motor manually. This start-up procedure complies with the requirements of the firefighting

standards.

Use this function only once. Repeated attempts could damage the engine

In order to activate the “commissioning” procedure, proceed as follows:

Set the selector switch to the “MAN” position.

Power the electric panel, then press and hold down the PROG / RESET / ENTER pushbutton
for longer than 5 seconds, you will access the PASSWORD parameter and the cursor will start

blinking.

Enter password PW2 and confirm by pressing the PROG/RESET/ENTER key.

Select the function using the UP / DOWN buttons and confirm by pressing the

PROG/RESET/ENTER key.

Enter the parameter value using the UP / DOWN buttons and confirm by pressing the

PROG/RESET/ENTER key.

WARNING