Installation

8.2.

Before installation

• The angle-seat control valve can be installed in any installation

position, preferably with the actuator in upright position.

• Before connecting the valve, ensure the pipelines are flush.
• Make certain the flow direction is correct (Flow direction always

below seat).

8.2.1. Preparatory work

Clean pipelines (Sealing material, swarf, etc.).

Devices with welded body
Remove the control unit from the actuator (if present):

Clamp the valve body in a holding device.

Loosen the fastening screws (2x).

Remove the control unit upwards.

Fastening screw
(2x)

Control unit

Actuator

Fig. 16: Disassembly the control unit

Remove the actuator from the valve body.

Install collet (white grommet) in pilot air port 1.

NOTE!

Damage to the seat seal or the seat contour!
• When removing the actuator, ensure that the valve is in open

position.

Control function A pressurize the pilot air port 1 with com-
pressed air (5 bar): valve opens.

Using a suitable open-end wrench, place the wrench flat on the
pipe.

Unscrew the actuator from the valve body.

Actuator

Nipple

Valve body

Flats for open-end

wrench

Pilot air port

CFA, CFB, CFI

Exhaust air port

CFA, CFB

Pilot air port CFI

2

1

Install collet:

Fig. 17: Installation

english