Maintenance, cleaning

10.

MAINTENANCE, CLEANING

10.1. Safety instructions

DANGER!

Danger – high pressure in the equipment!
• Before loosening the lines and valves, turn off the pressure and

vent the lines.

Risk of injury due to electrical shock!
• Before reaching into the system, switch off the power supply

and secure to prevent reactivation!

• Observe applicable accident prevention and safety regulations

for electrical equipment!

WARNING!

Risk of injury from improper maintenance!
• Maintenance may be performed by authorised technicians only!
• To screw on or unscrew valve body or actuator, use an open-

end wrench, never a pipe wrench, and observe tightening

torques.

Risk of injury from unintentional activation of the system and
an uncontrolled restart!
• Secure system from unintentional activation.
• Following maintenance, ensure a controlled restart.

WARNING!

For control function I – Danger if pilot pressure fails!
For control function I control and resetting occur pneumatically.
If the pressure fails, no defined position is reached.
• To ensure a controlled restart, first pressurize the device with

pilot pressure, then switch on the medium.

Risk of injury from moving parts in the device!
• Do not reach into openings.

10.2. Maintenance work

Actuator:
The actuator of the angle-seat control valve is maintenance-free
provided it is used according to these operating instructions.

Wearing parts of the angle-seat control valve:
Parts which are subject to natural wear:
• Valve seat
• Control cone
• Seals

If leaks occur, replace the particular wearing part with an appro-
priate spare part.
(For spare-part sets see chapter entitled “12. Replacement
parts”
).

The replacing of the wearing parts is described in chapter
“10.3. Replacing the wearing parts”.