Installation

NOTE!

Damage to the seat seal or the seat contour!
• When installing the actuator, ensure that the valve is in open

position.

Control function A pressurize the pilot air port 1 with com-
pressed air (5 bar): valve opens.

Screw actuator into the valve body.
Observe tightening torque (see “Tab. 16”).

1

2

Pilot air port

Fig. 19: Connections

Tightening torques of valve body / nipples
DN

Tightening torque [Nm]

15

45 ±3

20

50 ±3

25

60 ±3

32

65 ±3

40
50

70 ±3

65

100 ±3

Tab. 16: Tightening torques of valve body / nipples

8.3.3. Install control unit

Before installation, check the position of the ports on the
control unit and, if required, align the actuator.
Description see chapter “8.3.4. Rotating the actuator”.

Remove collet from pilot air port 1.

Check that the O-rings are correctly positioned in the pilot air
ports.

Align the puck holder and the control unit until
1. the puck holder can be inserted into the guide rail of the
control unit and
2. the supports of the control unit can be inserted into the pilot
air ports of the actuator (see also “Fig. 21”).

NOTE!

Damaged printed circuit board or malfunction!
• Ensure that the puck holder is situated flat on the guide rail.

Guide rail

Puck holder

Fig. 20: Aligning the puck holder