Malfunctions – Burkert Type 2300 User Manual

Page 39

Advertising
background image

39

Malfunctions

1

2

Pilot air port

Fig. 36: Connections

Tightening torques of valve body / nipples
DN

Tightening torques [Nm]

15

45 ±3

20

50 ±3

25

60 ±3

32

65 ±3

40
50

70 ±3

65

100 ±3

Tab. 20: Tightening torques of valve body / nipples

If the position of the pilot air ports for installation of the hoses
is unfavorable, these can be aligned steplessly by rotating
the actuator through 360°.
The procedure is described in the chapter entitled “8.3.4.
Rotating the actuator”.

11.

MALFUNCTIONS

Malfunction

Remedial action

Actuator does
not switch.

Pilot air port interchanged

14)

CFA:

Connecting pilot air port 1

CFB:

Connecting pilot air port 1

CFI

Pilot air port 1: Open
Pilot air port 2: Close

Pilot pressure too low
See pressure specifications on the type label.
Medium pressure too high
See pressure specifications on the type label.
Flow direction reversed
See direction arrow on the body.

Tab. 21: Malfunctions - 1

14)

See “Fig. 23: Pneumatic connection” .