AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

PAGE 5 - 74

Chapter 5: Control Interfaces

5.13 Input / Output Signal Layout using Toolsnet Version

InterBus-S, Devicenet & Profibus interfaces can be configured to be connected to the Atlas Copco
Toolsnet Network. If this setting is selected, the I/O signal mapping changes according to the
tables below. (If the Toolsnet version is selected during the interface board set-up (5.1), this I/O
mapping will be automatically set)

5.13.1 Special Configuration File

A special fieldbus configuration file called “toolsnet.fcf” file is provided for assigning I/O mapping
for toolsnet data output.
This file will configure the size and will automatically be set as 32 byte Output (FEC Inputs) and
128 bytes Input (FEC Outputs) and you cannot change the size.

Since the configuration is special, the setup screen does not show the value correctly.
It will show as below (disregard this screen).


Note: Configure the PLC I/O Length as 32 Byte / 16 Word Output (FEC Input) & 128 Byte / 64
Word Input (FEC Output)