AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

PAGE 5 - 25

Chapter 5: Control Interfaces

5.6.1 Component Descriptions

Fieldbus Interface Connection

Pin No.

Signal

Description

1

N.C.

2

N.C.

3

B- Line

Positive RxD/TxD according to RS485 Spec.

4

RTS

Request to send

5

GND Bus Isolated GND from RS 485 side

6

+5V Bus

Isolated +5V from RS 485 side

7

N.C.

8

A- Line

Negative RxD/TxD according to RS485 Spec.

9

N.C.

(9 pin female D-sub)

Housing Shield

Connected to PE

Termination

Termination of the fieldbus requires a terminating resistor at each end of the
fieldbus. A termination switch is provided on the Profibus-DP interface board. Set
the switch to “ON”, if termination is required. If external terminators are used, the
switch must be in the off position.

Node Address


Before configuring the Profibus-DP module, the node address has to be set. This is
done with two rotary switches on the module which can set the node address 1-99
in decimal format. The Upper rotary switch (closest to the D-sub) sets the “tens”
digit (10x), and the bottom rotary switch sets the “ones” digit (1x). Example: To set
node 37, place the “tens” digit switch on 3 and the “ones” digit switch on 7.
This switch must be set before power is on, and cannot be changed during
operation.


Status LEDs

LED

Status

Description

1

-

Not Used

2

Off

Module not on-line

Green

Module is on-line and data exchange is possible.

3

Off

Module is not off-line

Red

Module is off-line and data exchange is not
possible.

4

Fieldbus

Diagnostics

Off

No diagnostics present.

Red flashing at 1
second intervals

Error in configuration: IN and/or OUT length set
during initialization of the module is not equal to
the length set during configuration of the
network.

Red flashing at 1/2
second intervals

Error in user parameter data: The
length/contents of the User Parameter data set
during initialization of the module is not equal to
the length/contents set during configuration of
the network.

Red flashing at 1/4
second intervals

Error in initialization of the PROFIBUS
communication ASIC.

5

1

9

6

1

2

3

4