11 ethernet-i/p interface – FEC AFC1500 User Manual

Page 99

Advertising
background image

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

PAGE 5 - 55

Chapter 5: Control Interfaces

5.11 Ethernet-I/P Interface

The Ethernet-I/P communication interface allows slave connection to PLC networks that support
Ethernet communication via TCP/IP.
Maximum I/O data is 256 input bits & 256 output bits. FEC Inputs match the discrete input layout. FEC
Output location is programmed using the AFC User Console Software. Communication speeds of
10/100M baud (auto-selectable) are supported.

FEC integrates the Ethernet-I/P board manufactured by HMS Fieldbus Systems AB into the Multi-2
Unit’s modular I/O board. For further technical information on the Ethernet-I/P interface go to the HMS
website. (

www.hms.se

)





































Item

Description

1

Application Connector

2

Ethernet Connector

3

Configuration Switches

4

Status LEDs (4)

5

Watchdog LED

Red - (flashing @ 2Hz) - ASIC and FLASH ROM check fault.
Green (flashing @ 2Hz) - module not initialized.
Green (flashing @ 1Hz) - module initialized and running OK.
Red (flashing @ 1Hz) - RAM check fault.
Red (flashing @ 4Hz) - DPRAM check fault.

2

1

3

4

5

- Represents switch position

Advertising