AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

PAGE 5 - 51

Chapter 5: Control Interfaces

5.10.1 Component Descriptions


Fieldbus Interface Connection

Pin No.

Color

Description

1

Blue

COM Line

2

Clear

Ground

3

Shield

COM Line


Termination

Termination of the RIO network requires a terminating resistor at each end of the
network. A termination switch is provided on the front of the interface board. Set the
switch to “ON”, if termination is required. If external terminators are used, the switch
must be in the off position.

Configuration Switches


On an A-B Remote I/O network, each node must be assigned its own unique Rack Address. The
Rack Address is a value between 0 and 59 used to identify each node. The Rack Address and Baud
Rate are set using the DIP switches on the front of the module.
These switches must be set before power is on and cannot be changed during operation.

Baud Rate Settings

Baud Rate

SW-1

SW-2

57.6K

OFF

OFF

115K

ON

OFF

230K

OFF

ON

Reserved

ON

ON

Rack Address Settings

Rack

Address

SW-3

(MSB)

SW-4 SW-5 SW-6 SW-7

SW-8

(LSB)

Address 0

OFF

OFF

OFF

OFF

OFF

OFF

Address 1

ON

OFF

OFF

OFF

OFF

OFF

Address 2

OFF

ON

OFF

OFF

OFF

OFF

Address 3

ON

ON

OFF

OFF

OFF

OFF

Address 57

ON

OFF

OFF

ON

ON

ON

Address 58

OFF

ON

OFF

ON

ON

ON

Address 59

ON

ON

OFF

ON

ON

ON

Status LEDs

LED

State

Description

Error

OFF

Normal Operation

ON - Red

Bus off / Error

Active

OFF

No Communication

ON - Green

Communication Active

Power

OFF

Power Off

ON - Green

Power On

ON