AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

PAGE 5 - 19

Chapter 5: Control Interfaces

5.5.1 Component Descriptions

Fieldbus Interface Connections

Pin No.

Signal

Wire Color

1

V-

Black

2

CAN_L

Blue

3

Drain/Shield

4

CAN_H

White

5

V+

Red


Termination

Termination of the fieldbus requires a terminating resistor at each end of the fieldbus. These
resistors should have a value of 121 ohms.

Configuration Switches


On a DeviceNet network, each node must be assigned its own unique Mac ID. The Mac ID is a
value between 0 and 63 used to identify each node. The Mac ID and Baud Rate are set using the
DIP switches on the front of the module.
These switches must be set before power is on and cannot be changed during operation.

Baud Rate Settings

Baud Rate

SW-1

SW-2

125K

OFF

OFF

250K

OFF

ON

500K

ON

OFF

Reserved

ON

ON

Mac ID Settings

Mac ID

SW-3

(MSB)

SW-4 SW-5 SW-6 SW-7

SW-8

(LSB)

Address 0

OFF

OFF

OFF

OFF

OFF

OFF

Address 1

OFF

OFF

OFF

OFF

OFF

ON

Address 2

OFF

OFF

OFF

OFF

ON

OFF

Address 3

OFF

OFF

OFF

OFF

ON

ON

Address 61

ON

ON

ON

ON

OFF

ON

Address 62

ON

ON

ON

ON

ON

OFF

Address 63

ON

ON

ON

ON

ON

ON


Status LEDs

LED

State

Description

1 - Reserved

-

Reserved for future use.

2 - Network Status

Off

Not Powered / Not Online

Green solid

Link OK, Online, Connected

Green flashing

Online, Not connected

Red solid

Critical Link Failure

Red flashing

Connection Timeout

3 - Module Status

Off

No power to device

Green solid

Device operational

Green flashing

Data size bigger than configured

Red solid

Unrecoverable fault

Red flashing

Minor fault

4 - Reserved

-

Reserved for future use.

ON

8

5

4

2

3

7

6

1

1

2

3

4

See “Termination”