AFC1500 Multi-2 Unit Hardware Manual (Rev. 2)

PAGE 4 - 19

Chapter 4: Installation & Wiring

4.7.5 External DIP Switch

¦

¦

¦

¦

(Located on bottom of unit)

DIP SWITCH (Factory Setting)

(Bottom View)

4.8 Setting Default TCP/IP Address

¦

¦

¦

¦

User Console Ethernet Port

For Multi-2 units with firmware 1.16 or greater, the IP address for the User Console Ethernet Port can be
reset to the default setting by following the directions below.

1. Turn off power to the unit
2. Turn “ON” DIP Switch no. 1, 2 & 4
3. Depress and HOLD the RESET button (on front of unit) and turn the power back on
4. Hold the RESET button until the green ACC LED turns on solid
5. Turn power off and reset DIP Switch back to original setting


When power is reapplied, the TCP/IP settings will revert to the following default;

IP Address

: 192.168.10.10

Subnet Mask

: 255.255.255.0

Default Gateway

: 192.168.10.1

4.9 Firmware Flash Connector

Upgrades or revisions to firmware are handled easily with the on board Flash Connector located on

the bottom of each Multi-2 Unit. There is no need to remove or disassemble the unit. A flash adapter

(CONTROLLER-ROM) containing the new firmware can be connected to connector CN8 with the

power off to the unit. The power is then cycled on until the ACCEPT LED is blinking indicating the

firmware upload is complete. Turn off power and remove the flash adapter. The firmware update is

now complete.

Note: This connector is for FEC use only and it is not recommended for use other than FEC.

No.

OFF

ON

4

Not Used

3

Not Used

2

Angle resolution: 0.1 Angle resolution: 1

1

EXT. I/O ENABLE EXT. I/O DISABLE

FRONT

Switch 1: I/O Enable / Disable Test Mode

If Switch No.1 is turned ON, the Input / Output Module

will be bypassed and the STOP signal will be enabled

allowing Manual operations through the front panel

buttons for testing purposes. This is particularly

useful when Fieldbus interfaces are installed and

connection to the master device is not possible.

When finished testing the equipment, be sure to

turn Switch No. 1 OFF.

Do not change Switch No. 3 or 4.

Switch 2 : Angle Resolution

Normal angle resolution is 1.0 degree. Angle

resolution of 0.1 degree is available using this switch.

Note: SAN unit firmware version 3.3x is required and

the function enabled if using the AFC User Console for

monitoring purposes.