FEC AFC1500 User Manual

Page 82

Advertising
background image

AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

PAGE 5 - 38

Chapter 5: Control Interfaces

ON

8

5

4

2
3

7

6

1

ON

4

2
3

1

5.8.1 Component Descriptions

Fieldbus Interface Connection


Pin 1

DA

Communication Line

Pin 2

DB

Communication Line

Pin 3

DG

Digital Ground

Pin 4

SHIELD

Connect cable shield

Pin 5

FG

Field Ground

Mating Connector: Allows in-line “series” connection






Wiring of the CC-Link network should be performed by using the cable listed in the CC-Link
Specifications. The three twisted conductors should be wired in series to each CC-Link device,
using a terminating resistor at the Master end and on the last Remote/Local device between the DA
& DB terminals.

Termination


Termination of the CC-Link requires a terminating resistor at each end of the fieldbus. Connect 120
ohm resistor between the DA & DB terminals if this is the last connection. (Remember that the CC-
Link master also needs to be terminated)

Station Number Setting (SW1)


Station Number switch sets the address in the CC-Link network. Max. number of stations is 64. No
two devices may share the same address. Switch setting format is Binary Coded Decimal (BCD)
Switch 1-4 is Least Significant Byte (LSB). Switch 5-8 is Most Significant Byte (MSB).

SW-1 SW-2 SW-3 SW-4 SW-5 SW-6 SW-7 SW-8

Station #

ON

OFF

OFF

OFF

OFF

OFF

OFF

OFF

1

OFF

ON

OFF

OFF

OFF

OFF

OFF

OFF

2

.

.

.

.

.

.

.

.

.

OFF

OFF

OFF

OFF

ON

OFF

OFF

OFF

10

.

.

.

.

.

.

.

.

.

ON

ON

ON

OFF

OFF

OFF

ON

OFF

47

.

.

.

.

.

.

.

.

.

OFF

OFF

ON

OFF

OFF

ON

ON

OFF

64

This switch must be set before power is on and cannot be changed during operation.

Baud Rate Setting (SW2)

Baud rate

SW-1

SW-2

SW-3

SW-4

156K

OFF

OFF

OFF

OFF

625K

ON

OFF

OFF

OFF

2.5M

OFF

ON

OFF

OFF

5M

ON

ON

OFF

OFF

10M

OFF

OFF

ON

OFF

This setting MUST match the setting of the Master module. This switch must be set before
power is on and cannot be changed during operation.

Manufacturer

:Phoenix Contact

Model Name

:TMSTBP 2.5/5-ST-5.08


*Connector is attached.

See

“Termination”

Advertising