AFC1500 Multi-2 Unit Hardware Manual (Rev2.1)

PAGE 5 - 39

Chapter 5: Control Interfaces

ON

4

2
3

1

Number of Occupied Stations (SW3)


Occupied Stations setting determines the number of 32 bit station buffer memory locations that will
be allocated for this station in the Master buffer memory. This sets the number of total I/O available
for the station. Each memory bit has a designated input AND output buffer. So a setting of (1) 32
station actually allocates 32 input & 32 output locations for a total of 64 total points. This switch must
be set before power is on, and cannot be changed during operation.

NOTE: See FEC Electrical Controls drawings for actual setting required as this may vary per
application.

Number of Stations

SW-1

SW-2

SW-3

SW-4

1 (32 In/32 Out)

ON

ON

ON

OFF

2 (64 In/64 Out)

ON

OFF

ON

OFF

3 (96 In/96 Out)

OFF

ON

ON

OFF

4 (128 In/128 Out)

OFF

OFF

ON

OFF




Status LEDs


RUN

OFF

Watchdog Timer error

ON

Module is Normal - Running

ERR

OFF

Normal

ON - Steady

Communication error at all
Stations

ON - Flashing

Communication error at Station

SD

Send Data

Module Sending Data

RD

Read Data

Module Reading Data