Air heater requirements, Ransburg – Ransburg RMA-560 Single_Dual Purge Direct A13364 User Manual

Page 28

Advertising
background image

AIR HEATER REQUIREMENTS

Turbine drive air expands as it moves through the

turbine wheel cavity and as it exits the turbine from

the exhaust port. This expansion will cause cool-

ing of the exhaust air and the surfaces it contacts.

This same expansion cooling can occur across the

shaping air exit ports. This cooling affect can cause

surface temperatures to fall below the dew point

of the booth, which will result in condensation on

the interior and exterior of the atomizer, machine,

and its components. It is even possible that the

temperature of the supply air may be below the

booth dew point, even without additional expan-

sion cooling.

Condensation is especially probable in waterborne

applications when booth temperature and relative

humidity levels are typically maintained very high.

This condensation will allow sufficient conductivity

of the surfaces such that they act as an erratic

ground source potential. This can cause damage

to the equipment.

It is therefore, a requirement that turbine exhaust

air temperature be maintained above the booth

dew point to prevent condensation from forming

on atomizer surfaces. Doing so will eliminate

moisture as a potential defect in painted surfaces

as well as extending equipment life. Thus, it is

recommended that air heaters be installed into

the atomizer air supply lines, i.e. turbine drive air,

shaping air, and seal air. The air heaters must

be of sufficient capacity, capable of raising the

incoming air temperature at least 40°F (4.4°C) at

a flow rate of 60 SCFM per applicator.

The actual air heater process setting depends on

applicator fluid flow rate load, booth conditions,

turbine airflow settings, and incoming air tempera-

ture. The heater should be set as low as possi-

ble, sufficient to maintain the applicator surface

temperatures above the dew point in the booth.

Example: With the incoming air temperature at

72°F (22.2°C), and RMA-560 with 65mm bell cup

rotating unloaded at 60 krpm has a turbine outlet

temperature drop of approximately 28°F (-2.2°C)

@ 40 krpm unloaded, ∆~14°F (-10°C). Referring

to the ASHRAE Psychrometric chart, the saturation

temperature range (dew point) of a spray booth

maintained at 70-75°F/65-70% RH is 62-68°F

(21.1-23.9°C/65-70°RH is 16.7-20°C). Thus it is

almost certain that the surface temperatures of

the applicator will fall below the dew point of the

booth, and an air heater will be needed in this case.

To prevent condensation, a Ransburg air heater

assembly should be assembled after the air filters

and volume booster. (See heater and filtration

options later in this manual).

SAFE GROUNDING IS A MATTER OF PROPER

EQUIPMENT MAINTENANCE AND INSTAL-

LATION, CORRECT OPERATION AND GOOD

HOUSEKEEPING. Daily inspection of grounding

apparatus and conditions, however, will help pre-

vent hazards that are cause by normal operations.

BE SURE THAT:

1. All objects in the spray area are grounded.

2. Personnel in the spray area are properly

grounded. (Conductive safety shoes and

coveralls.)

3. That the target object is properly grounded

(less than 1 megohm resistance).

4. That the high voltage is off except during

normal application.

5. That the high voltage is off and applicators

are grounded during maintenance opera-

tions.

6. The spray area is kept free of accumulated

coating deposits.

7. All combustible liquids in the spray area

(outside of automatic delivery systems) are

kept to minimum and are kept in fire safe,

grounded containers. (See NFPA-30 and

chapter 6 of NFPA-33.)

8. Proper ventilation is provided.

9. Personnel must thoroughly understand the

equipment, its operation and maintenance,

and all safety precautions.

RMA-560 Single/Dual Purge Direct Charge - Installation

Ransburg

LN-9278-13

25

Advertising