Interlocks, Ransburg – Ransburg RMA-560 Single_Dual Purge Direct A13364 User Manual

Page 36

Advertising
background image

INTERLOCKS

The following system interlocks are required to

prevent equipment damage.

Bearing air should remain on at all times

and should be shut-off by turning off the

main air to the pneumatic control cabinet.

It should not be possible for the coating

material to be sprayed unless the turbine is

spinning.

Two inter-connected bearing air ports are

provided, one for supply air and the other

to be used as a return signal for measur-

ing bearing air pressure at the atomizer. If

bearing air falls below 80 psi (551.6 kPa)

at the atomizer, the turbine air should be

automatically interlocked to shut off. This

interlock is provided by the Serial Atomizer

Module. (See current “Serial Atomizer” ser-

vice manual.)

High voltage must be interlocked with the

solvent valve pilot signal to prevent solvent

flow while high voltage is energized (direct

charge only).

Turbine air and brake air must be inter-

locked to prevent both from being used si-

multaneously. This interlock is provided by

the Serial Atomizer Module. (See current

“Serial Atomizer” service manual.)

Any other interlocks required by local na-

tional code or international code. The fol-

lowing system interlocks are required to

prevent equipment damage:

C A U T I O N

!

W A R N I N G

!

†

The high voltage and/or coating materi-

al must never be turned on unless the bell

cup is mounted on the motor shaft and the

turbine is rotating.

†

Pneumatic input to the turbine air inlet

must be controlled to prevent the turbine

from exceeding the maximum rated speed

of 80,000 rpm. (See “Specifications” in the

“Introduction” section.)

†

High voltage must never be turned on

while cleaning solvent is being sprayed

either through the applicator supply or

the cup wash line. High voltage and both

solvent triggers must be interlocked (direct

charge only).

†

Never spray solvent with high voltage on.

†

When the turbine air is turned off, the tur-

bine will continue to operate or “coast down”

for about two minutes. Provisions should be

made to assure that the operator waits at least

three minutes, after shutting off the turbine air

and before shutting off the main air supply.

†

The bell cup must be removed when

making flow checks. If the paint is turned

on when the bell is mounted and the turbine

shaft is not rotating, paint will enter the shaft

and possibly damage the air bearing. Mate-

rial flow checks (flow rate verification) must

be made with the bell cup off and the turbine

not rotating. Normally pneumatic interlocks

will not allow the paint to trigger on when the

turbine air is off.

RMA-560 Single/Dual Purge Direct Charge - Installation

Ransburg

LN-9278-13

33

Advertising