36

3-1-1 Push Force at Standstill


To operate the actuator in the push mode, enter a current limit value (%) in the “Push” field of the position data
table.
With E-Con controllers, the push force at standstill must correspond to approx. 70% of the current limit value.
You can increase/decrease the push force at standstill by increasing/decreasing the current limit value, but the
controller will not operate normally if the current limit value is set to 30% or below.
The table below lists the push forces at standstill of rod-type RCS actuators based on a current limit value of
70%.

Type

Motor

W

Speed type

Push force N (kgf)

L

178(18.2)

M

89(9.1)

60

H

44(4.5)

L

296(30.3)

M

149(15.2)

RA55

100

H

74(7.6)

L

238(24.3)

M

118(12.1)

60

H

59(6.1)

M

198(20.2)

RB7530

100

H

99(10.1)

L

296(30.3)

M

149(15.2)

100

H

74(7.6)

M

222(22.7)

Rod type

RB7535

150

H

111(11.4)

L

178(18.2)

M

89(9.1)

60

H

44(4.5)

L

296(30.3)

M

149(15.2)

Flat type

F55

100

H

74(7.6)



Caution:

Precision of push force at standstill is not guaranteed. The above figures are provided only for
reference.