(2) Communication

Speed

Name Symbol Unit

Input range

Default value

(reference)

Communication speed

BRSL

bps

9600~115200

38400


This parameter sets the speed of communication with the PC software.

Communication speeds that can be set = 9,600/19,200/38,400/57,600/115,200 bps

(3) Flag for Setting Function at Stop

Name Symbol Unit

Input range

Default value

(reference)

Flag for setting function

at stop

FSTP (Bit

input) 000~111b

[A]

101b

(actuator without brake)

111b

(actuator with brake)


This parameter sets the function activated at a stop operation where the servo is turned off.

Bit No.

Function

Setting

Status

0

Disabled Disable a dynamic brake.

2 Dynamic

brake

1

Enabled Enable a dynamic brake.

0

Disabled Disable an electromagnetic brake.

1 Electromagnetic

brake

1

Enabled Enable an electromagnetic brake.

0

Disabled Do not clear the deviation counter.

0

Deviation counter clear

(when the servo is turned off

and an alarm is generated)

1

Enabled Clear the deviation counter.




z

When the electromagnetic brake bit is set to “Enabled,” an “electromagnetic brake not released error”

is output and operation is cancelled if the electromagnetic-brake power is not supplied.

z

Always set the electromagnetic brake bit to “Disabled” when using P-Driver together with an actuator

that is not equipped with an electromagnetic brake.

(4) Software Stroke Limit

Name Symbol Unit

Input range

Default value

(reference)

Software stroke limit,

positive side (actual

stroke)

LIMM pulse

134217727~

134217728

[A]

Software stroke limit,

negative side (actual

stroke)

LIML pulse

134217727~

-134217728

[A]


Set the upper and lower limits of the actual stroke (catalog values) of the actuator in pulse values. At
shipment from the factory, appropriate values corresponding to the applicable actuator have been set.