7.2.3 Alarms

(1) Alarm

Levels


Alarms are classified into the following three levels according to the error description:

Alarm level

Alarm code

(HEX)

ALM LED

Condition at occurrence

Cancellation method

Message 900~AFF

Turned

off

Alarm display in the PC software
(The actuator is not stopped.)

Operation

cancellation

B00~CFF Turned

on

The actuator is forcibly
stopped.

(The actuator decelerates to
a stop and the servo is turned
off. The homing completion
status is canceled.)

Reset the controller using
the alarm reset signal (RES)
or the PC software.

(It is necessary to perform
homing operation again.)

Cold start

D00~FFF Turned on

The actuator is forcibly
stopped.

(The actuator decelerates to
a stop and the servo is turned
off. The homing completion
status is canceled.)

Turn the power supply off
and back on again.

(It is necessary to perform
homing operation again.)


+

Cancel the alarm after investigating and removing the cause in all the cases.


+

Contact IAI if the cause of an alarm cannot be removed or an alarm cannot be canceled even if the

cause is removed.





z

If the same error occurs after canceling an alarm, the cause of the alarm has not been removed. Try

removing the cause and canceling the alarm again.



Caution