7.2.1 Errors

Occurring

when

Turning the Power Supply on


When the prescribed power is supplied to the main power supply of P-Driver, the RDY LED of the status
indicator turns on.

+

Contact us if the RDY LED does not turn on even if the prescribed power is supplied (please check the

voltage).


7.2.2 Errors

Without

Alarm

Display


The ALM LED of the status indicator on the front of P-Driver is not lit. No alarm has been generated even
with the PC software connected.

(1) The Actuator does not Operate








































YES

YES

YES

YES

NO

NO

NO

NO

The actuator does not operate

Is the pulse-train

output interface of the

host controller a

differential line driver?

Is the RDY LED lit?

Is the RUN LED lit?

Is each signal of the

I/O interface, including

the pulse train,

operating normally?

Set the command pulse-train mode properly

using the corresponding parameter.

Contact IAI.

The servo is not turned on.
Check the connection of the power supply of
I/O interface (24 VDC) and the I/O cable.

Check the pull-up resistance value in
the case of an open collector.

Check the input signals.