A.14, See p. a.14, Appendix – Watlow MICRODIN User Manual

Page 100: Primary control output (heating or cooling), Alarm output, Accuracy, Safety agency approvals, Electromagnetic compatibility and immunity, Terminals, Power

Advertising
background image

Appendix

A . 1 4 Wa t l o w M i c r o D I N

Primary Control Output (heating or cooling)

• Output update rate: 10 per second, 10Hz (maximum)

Internal Load Switching (nominal):
Switched dc (isolated) signal, 22 to 28VÎ (Vdc), current limited @ 30mA
Overload current and short circuit protection
External Load Switching (maximum):

• Open Collector 60VÎ (Vdc) @ 1A

Alarm Output

• Output update rate 2 per second (2Hz)
• Electromechanical relay, Form A, 2A @ 30VÎ (Vdc) or 240VÅ(Vac),
• Alarm output can be latching or non-latching, and process or deviation with

separate high and low values. Alarm silencing (inhibit) on power-up.

Accuracy

• Calibration accuracy and sensor conformity: ±0.1% of span ±1 @ 77°F ±5°F (25°C

±3°C) ambient, and rated line voltage ±10% with the following exceptions:
Type T; 0.12% of span for -200°C to -50°C
Types R and S; 0.15% of span for 0°C to 100°C
Type B; 0.24% of span for 870°C to 1700°C

• Accuracy span: Less than or equal to operating ranges, 1000°F/540°C minimum.
• Temperature stability: ±0.2°F/°F (±0.2°C/°C) rise in ambient maximum for

thermocouples, ±0.05°F/°F (±0.05°C/°C) rise in ambient maximum for RTD sensors

• Voltage stability: ±0.01% of span per percent of rated line voltage

Safety Agency Approvals

• UL/C-UL 508, File # E102269

Industrial Control Equipment

• CE to EN 61010 (pending)

Electromagnetic Compatibility and Immunity

• Complies with EN 50081, EN 50082

Terminals

• Touch-safe set screw type, accepts 26 to 14 gauge wire

Power

• 24-28V‡(Vac/Vdc), -15%, +10% [20.4 to 30.8V‡(Vac/Vdc)]; 50/60Hz ±5% for VÅ(Vac)
• 5VA typical power consumption
• Data retention upon power failure via nonvolatile memory
• Sensor input isolation to switched dc output and communication circuitry

500VÅ(Vac) dielectric

Operating Environment

• 32 to 149°F (0 to 65°C)
• 0 to 90% RH, non-condensing
• Storage temperature: -40 to 158°F (-40 to 70°C)

Dimensions

• Width x Height x Depth

1.64" x 4.65" x 5.19" DIN rail mount
(42mm x 118mm x 132mm)
1.64" x 4.65" x 5.06" Chassis mount
(42mm x 118mm 129mm)

• Mounts on DIN rail per DIN EN 50022 (35mm x 7.5mm)

UL

®

is a registered trademark of Underwriters Laboratories.

Modbus

is a registered trademark of AEG Schneider Automation.

Adobe

®

and Acrobat

®

are registered trademarks of Adobe Systems Incorporated.

These specifications are subject to change without prior notice.