Parameters

= R e a d O n l y ;

= R e a d / W r i t e ;

= Tu r n O n / O f f

Wa t l o w M i c r o D I N 5 . 1 5

ON

PID Group continued

about PID control.

• Read/write
• Modbus: 502

Range

0.00 to 99.99 minutes per repeat

Default

0.00

Active

if Propband (PID Group) is not set to 0 and Units Type (System
Group) is set to US

Affected by

Changing Units Type (System Group) will convert Integral to

Reset.

Derivative

• Set the derivative time for PID control. See

Chapter 4

for

information about PID control.

• Read/write
• Modbus: 503

Range

0.00 to 9.99 minutes

Default

0.00

Active

if Propband (PID Group) is not set to 0 and Units Type (System
Group) is set to SI

Rate

• Set the rate time for PID control. See

Chapter 4

for information

about PID control.

• Read/write
• Modbus: 504

Range

0.00 to 9.99 minutes

Default

0.00

Active

if Propband (PID Group) is not set to 0 and Units Type (System
Group) is set to US