Reset, Derivative, Rate – Watlow MICRODIN User Manual
Page 63: Parameters, Pid group continued
Parameters
= R e a d O n l y ;
= R e a d / W r i t e ;
= Tu r n O n / O f f
Wa t l o w M i c r o D I N 5 . 1 5
ON
PID Group continued
about PID control.
• Read/write
• Modbus: 502
Range
0.00 to 99.99 minutes per repeat
Default
0.00
Active
if Propband (PID Group) is not set to 0 and Units Type (System
Group) is set to US
Affected by
Changing Units Type (System Group) will convert Integral to
Reset.
Derivative
• Set the derivative time for PID control. See
for
information about PID control.
• Read/write
• Modbus: 503
Range
0.00 to 9.99 minutes
Default
0.00
Active
if Propband (PID Group) is not set to 0 and Units Type (System
Group) is set to SI
Rate
• Set the rate time for PID control. See
for information
about PID control.
• Read/write
• Modbus: 504
Range
0.00 to 9.99 minutes
Default
0.00
Active
if Propband (PID Group) is not set to 0 and Units Type (System
Group) is set to US