Parameters restore to factory calibration (set), Reset factory defaults (set), Calibration group continued – Watlow MICRODIN User Manual
Page 79
Advertising
= R e a d O n l y ;
= R e a d / W r i t e ;
= Tu r n O n / O f f
Wa t l o w M i c r o D I N 5 . 3 1
ON
Parameters
Restore to Factory Calibration (Set)
• Restore factory calibration values from the backup memory.
• Write
• Modbus: 1601
Range
0: no action
1: restore factory calibration
Default
0 (always reads 0)
Active
if the controller is in the calibration mode
Reset Factory Defaults (Set)
• Reset all parameters to factory values.
• Read/write
• Modbus: 1602
Range
0 to 799 and 801 to 999: no action
800: reset parameters to factory values
Default
0
Active
if the controller is in calibration mode
Calibration Group continued