Parameters

= R e a d O n l y ;

= R e a d / W r i t e ;

= Tu r n O n / O f f

Wa t l o w M i c r o D I N 5 . 5

ON

Input Group continued

Input Group – Setup

Sensor Type

• Select the input sensor type.
• Read/write
• Modbus: 600

Range

0: thermocouple
1: RTD

Default

0: thermocouple

Active

always

Affects

Changes Input Type (Input Group) to J for thermocouple, DIN

for RTD, and defaults temperature related parameters.

Input Type

• Set the linearization for the input sensor.
• Read/write
• Modbus: 601

Range

if Sensor Type (Input Group) set to thermocouple

0: J
1: K
2: T
3: E
4: N
5: C
6: D
7: PT2
8: R
9: S
10: B

if Sensor Type (Input Group) set to RTD

11: RTD_DIN
12: RTD_JIS

Default

if Sensor Type (Input Group) is changed to thermocouple: J
if Sensor Type (Input Group) is changed to RTD: DIN

Active

always

Affected by

Changing Sensor Type sets to J for thermocouple, DIN for RTD,

and defaults temperature related parameters