Loop back command (0x08), Appendix – Watlow MICRODIN User Manual

Page 91

Advertising
background image

Packet sent to controller: | nn | 10 | nn nn | 00 01 | 02 | nn nn | nn nn |

∆ ∆

∆ ∆

∆ ∆

∆ ∆

controller address (one byte)

write to multiple registers command (0x10)

starting register high byte

starting register low byte

number of registers to write high byte (0x00)

number of registers to write low byte (must be 0x01)

number of data bytes (must be 0x02)

data high byte

data low byte

CRC low byte

CRC high byte

Packet returned by controller: | nn | 10 | nn nn | 00 01 | nn nn |

∆ ∆

∆ ∆

∆ ∆

controller address (one byte)

write to multiple registers command (0x10)

starting register high byte

starting register low byte

number of registers to write high byte (0x00)

number of registers to write low byte (must be 0x01)

CRC low byte

CRC high byte

Loop Back Command (0x08)

This command simply echoes the message. This serves as a quick way to check
your wiring.

Packet sent to controller: | nn |

08 | nn nn | nn nn |

∆ ∆

∆ ∆

controller address (one byte)

loop back command (0x08)

data high byte

data low byte

CRC low byte

CRC high byte