Wa t l o w M i c r o D I N 5 . 3

ON

System Group – Setup

Units Type

• Select US or SI units of measurement.
• Read/write
• Modbus: 900

Range

0: US (reciprocate integral term)
1: SI (reciprocate integral term)

Default

0: US

Active

always

Affects

Propband, Integral and Reset (PID Group)
converts Reset and Integral (changes span to degrees or vice

versa)

C or F

• Select the temperature scale for the input.
• Read/write
• Modbus: 901

Range

0: F (Fahrenheit)
1: C (Celsius)

Default

0: F

Active

always

Decimal Point

• Sets the position of the decimal point for input readings.
• Read/write
• Modbus: 606

Range

0: decimal 0000 (for thermocouple and RTD)
1: decimal 000.0 (for for thermocouple and RTD)

Default

0

Active

if Sensor Type (Input Group) is set to RTD or thermocouple

System Group continued