Alarm Output Group continued

Alarm Output Group – Setup

Alarm Low

• Set the low alarm set point.
• Read/write
• Modbus: 321

Range

process: sensor range low to Alarm High (Alarm Output Group)
deviation: -1999 to -1

Default

process: sensor range low
deviation: -1999

Active

if Alarm Output Function (Alarm Output Group) is set to alarm

Affected by

Sensor Type (Input Group) determines range of setting and

default.

Input Type (Input Group) determines range of setting and

default.

Alarm Type (Alarm Output Group) determines range of setting

and default.

C or F (System Group) converts and determines range of setting.

Alarm High

• Set the high alarm set point
• Read/write
• Modbus: 322

Range

process: Alarm Low (Alarm Output Group) to sensor range high
deviation: 1 to 9999

Default

process: sensor range high
deviation: 9999

Active

if Alarm Output Function (Alarm Output Group) is set to alarm

Affected by

Sensor Type (Input Group)

determines range of setting and default

Input Type (Input Group)

determines range of setting and default

Alarm Type (Alarm Output Group)

determines range of setting and default

C or F (System Group)

converts and determines range of setting