Parameters

5 . 1 6 Wa t l o w M i c r o D I N

= R e a d O n l y ;

= R e a d / W r i t e ;

= Tu r n O n / O f f

ON

PID Group continued

Cycle Time

• Set the control output cycle time in seconds.
• Read/write
• Modbus: 506

Range

0.1 to 60.0 seconds

Default

2.0

Active

if Propband (PID Group) is not set to 0 and Units Type (System
Group) is set to US

Control Output Hysteresis

• Set the control output switching hysteresis.
• Read/write
• Modbus: 507

Range

1 to 9999°F or °C

Default

3

Active

only if Propband is set to 0