Error group – setup, Parameters, Input error action – Watlow MICRODIN User Manual

Page 72: Error clearing mode

Advertising
background image

Parameters

5 . 2 4 Wa t l o w M i c r o D I N

= R e a d O n l y ;

= R e a d / W r i t e ;

= Tu r n O n / O f f

ON

Error Group – Setup

Input Error Action

(see also Input Group)

• Select how the controller responds to an input error.
• Read/write
• Modbus: 902

Range

0: bumpless transfer (control output power remains constant,

Chapter 4

)

1: switch to the Fixed Manual Output (Control Output Group)
setting
2: shut off output

Default

0: bumpless transfer

Active

always

Error Clearing Mode

• Set the error clearing mode. When errors are latched, the error

message or indicator persists until it has been cleared manually.
Otherwise the error message or indicator clears automatically
when the condition that caused it no longer exists.

• Read/write
• Modbus: 607

Range

0: not latched (errors clear automatically)
1: latched (errors must be cleared manually)

Default

0: errors clear automatically

Active

always

Error Group continued