Wa t l o w M i c r o D I N 2 . 5

Communications

Setup

MicroDIN, A Modbus

™

Remote Terminal Unit (RTU)

RTU

The MicroDIN uses Modbus

™

RTU (remote terminal unit) protocol to read and

write to registers that can be viewed or changed from a personal computer.
Sending ASCII text commands to the MicroDIN will not work.

Access Via Registers

Each MicroDIN parameter has a corresponding Modbus

™

register and access

privileges. The value of each parameter is stored in a Modbus

™

register. The

access privilege — read only, write only or read/write — determines whether you
can change and/or view a parameter’s value.

Chapter 5

explains some of the

interactions between parameters. The tables at the end of this chapter show the
parameters and their setup order.

MicroDIN Supports...

Multiple Register Reads

MicroDIN supports Modbus

™

Commands 03 and 04 read of a 1- to 32-register

block. Responses from -1999 to 9999 are valid data for up to 32 register writes.

Modbus

™

32000 Errors

A Modbus

™

read command response of -32000 indicates that a register is not

implemented; -32001, register not active; or -32002, not read accessible.

Single Register Writes

MicroDIN supports a Modbus

™

write command (06) to a single register.

Multiple Register Writes

MicroDIN supports a Modbus

™

write command (16) for multiple writes as long

as the data length is 1.

Writing to address 0 broadcasts to all devices on the network.

Write Exceptions

MicroDIN supports write exceptions: 01, illegal function; 02, illegal register; 03,
illegal data.

Loop Back

MicroDIN supports a Modbus

™

write command 08, “loop back” to echo a

message.

Compatible Software

You will need compatible software to interact with a MicroDIN controller. One
such program is included with the MicroDIN Startup Kit. If you are accustomed
to using a Modbus

™

, see the Appendix for information to help write your own

Modbus

™

software application.

ç

CAUTION:

Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

See Disable Non-
volatile Memory
(System Group),
Ch. 5.