RTD Lead Compensation Analog-to-Digital Counts
• Reads the raw, RTD lead compensation, analog-to-digital converter
counts.
• Read only
• Modbus: 1502
Range
0 to 65535
Default
none
Active
always
RTD Lead Resistance
• Reads the measured RTD lead resistance in 0.01 ohms.
• Read only
• Modbus: 1503
Range
0.00 to 99.99
Default
none
Active
always
Proportional Term
• Monitor the proportional term. See
for information
about PID control.
• Read only
• Modbus: 205
Range
-100.0 to 100.0
Default
none
Active
always
Integral Term
• Monitor the integral term. See
for information about
PID control.
• Read only
• Modbus: 206
Range
heat: 0.0 to 100.0
cool: -100.0 to 0.0
Default
none
Active
always
Diagnostics Group continued