Communications

Setup

Set Address/Baud Rate

Configure the communications speed and network address of the MicroDIN
controller with the eight-bit DIP switch on the top panel. Set the controller
address with the first six switches. Set an address between 1 and 63. The
network will not work correctly if any two controllers have the same address.
DIP switch 1 sets the left-most binary digit. Switch 6 sets the right-most digit.

Record the MicroDIN’s address in erasable marker on the white space
on the front of the unit.

The seventh switch has no effect.

Set the network speed (9,600 or 19,200 baud) with the eighth switch.

Figure 2.7 -
MicroDIN top view with
DIP switches and baud
settings

O
N

1 2 3 4 5 6 7 8

Top View

Table 2.7 -
Decimal-to-binary
conversion

Dec.

Binary

1

000001

2

000010

3

000011

4

000100

5

000101

6

000110

7

000111

8

001000

9

001001

10

001010

11

001011

12

001100

13

001101

14

001110

15

001111

Dec.

Binary

16

010000

17

010001

18

010010

19

010011

20

010100

21

010101

22

010110

23

010111

24

011000

25

011001

26

011010

27

011011

28

011100

29

011101

30

011110

31

011111

Dec.

Binary

32

100000

33

100001

34

100010

35

100011

36

100100

37

100101

38

100110

39

100111

40

101000

41

101001

42

101010

43

101011

44

101100

45

101101

46

101110

47

101111

Dec.

Binary

48

110000

49

110001

50

110010

51

110011

52

110100

53

110101

54

110110

55

110111

56

111000

57

111001

58

111010

59

111011

60

111100

61

111101

62

111110

63

111111

O
N

1 2 3 4 5 6

7 8

O
N

1 2 3 4 5 6

7 8

O
N

1 2 3 4 5 6

7 8

O
N

1 2 3 4 5 6

7 8

O
N

1 2 3 4 5 6 7

8

O
N

1 2 3 4 5 6 7

8

9600 baud
(bit 8 on)

19.2k baud
(bit 8 off)

Advertising