Write to a single register command (0x06), Write to multiple registers command (0x10), Appendix – Watlow MICRODIN User Manual

Page 90

Advertising
background image

A . 4 Wa t l o w M i c r o D I N

Example: Read register 0 (model number) of the controller at address 1.

Sent:

01 03 00 00 00 01 84 0A

Received:

01 03 02 03 DC B9 2D

Message:

988 (0x03DC).

Example: Read register 1 and 2 (Process 1 and 2 values) of controller at address
5.

Sent:

05 03 00 01 00 02 94 4F

Received:

05 03 04 00 64 00 C8 FF BA

Message:

100 (0x0064) and 200 (0x00C8).

Write to a Single Register Command (0x06)

This command writes a parameter to a single register. The controller will echo
back the command. An attempt to write to a read-only parameter returns an
illegal data address error (0x02).

Packet sent to controller:| nn | 06 | nn nn | nn nn | nn nn |

∆ ∆

∆ ∆

∆ ∆

controller address (one byte)

write to a register command (0x06)

register high byte

register low byte

data high byte

data low byte

CRC low byte

CRC high byte

Example: Set register 7 (SPI) to 200 (0x00C8) on controller at address 9.

Sent:

09 06 00 07 00 C8 38 D5

Received:

09 06 00 07 00 C8 38 D5

Write to Multiple Registers Command (0x10)

This command actually writes a parameter to only a single register. An attempt
to write to a read-only parameter returns an illegal data address error (0x02).

Appendix