Parameters, Power limit set point, High side power – Watlow MICRODIN User Manual
Page 57: Control output group continued
Parameters
Control Output Group continued
= R e a d O n l y ;
= R e a d / W r i t e ;
= Tu r n O n / O f f
Wa t l o w M i c r o D I N 5 . 9
ON
Range
0: heat
1: cool
Default
0: heat
Active
always
Affects
Manual Output Power (Operation Group) determines heat or
cool values.
High Side Power, Low Side Power or Fixed Manual Output
(Control Output Group) changes range
Power Limit Set Point
• Select the set point that High Side Power and Low Side Power
(Control Output Group) will use to limit the control output range.
• Read/write
• Modbus: 713
Range
Range Low to Range High (Input Group) values
Default
Range High
Active
always
High Side Power
• Set the maximum allowed power above the Power Limit Set Point
(Control Output Group).
• Read/write
• Modbus: 714
Range
heat: 0.0 to 100.0
cool: -100.0 to 0.0
Default
heat: 100.0
cool: -100.0
Active
always
Affected by
Changing Control Output Function (Control Output Group)
changes range.