Parameters, Power limit set point, High side power – Watlow MICRODIN User Manual

Page 57: Control output group continued

Advertising
background image

Parameters

Control Output Group continued

= R e a d O n l y ;

= R e a d / W r i t e ;

= Tu r n O n / O f f

Wa t l o w M i c r o D I N 5 . 9

ON

Range

0: heat
1: cool

Default

0: heat

Active

always

Affects

Manual Output Power (Operation Group) determines heat or

cool values.

High Side Power, Low Side Power or Fixed Manual Output

(Control Output Group) changes range

Power Limit Set Point

• Select the set point that High Side Power and Low Side Power

(Control Output Group) will use to limit the control output range.

• Read/write
• Modbus: 713

Range

Range Low to Range High (Input Group) values

Default

Range High

Active

always

High Side Power

• Set the maximum allowed power above the Power Limit Set Point

(Control Output Group).

• Read/write
• Modbus: 714

Range

heat: 0.0 to 100.0
cool: -100.0 to 0.0

Default

heat: 100.0
cool: -100.0

Active

always

Affected by

Changing Control Output Function (Control Output Group)

changes range.