Parameters

5 . 6 Wa t l o w M i c r o D I N

= R e a d O n l y ;

= R e a d / W r i t e ;

= Tu r n O n / O f f

ON

Range Low

• Set the input range low. This setting is the lowest value that the

set point can have.

• Read/write
• Modbus: 602

Range

see Sensor Table in the Appendix for sensor ranges and defaults

Default

see Sensor Table in the Appendix for sensor ranges and defaults

Active

always

Affects

Set Point (Operation Group) limits the set point to the range

between Range Low and Range High (Input Group)

Range High

• Set the input range high. This setting is the highest value that the

set point can have.

• Read/write
• Modbus: 603

Range

see Sensor Table in the Appendix for sensor ranges and defaults

Default

see Sensor Table in the Appendix for sensor ranges and defaults

Active

always

Affects

Set Point (Operation Group) limits the set point to the range

between Range Low and Range High (Input Group)

Calibration Offset

• Set the input calibration offset. This allows you to compensate for

lead resistance, sensor errors and other factors.

• Read/write
• Modbus: 605

Range

-1999 to 9999

Default

0

Active

always

Input Group continued